Dry Ryser Inlet
The Dry Riser Inlet (Breeching Inlet) is a vital component of fire protection systems used in multi-storey buildings to supply water to the dry riser pipeline during firefighting operations. It allows firefighters to connect hoses from fire engines and pump water into the building’s fire safety system. Manufactured from high-quality ductile iron, gun metal, or stainless steel, the dry riser inlet is designed for durability, corrosion resistance, and reliable performance. Available in 2-way, 3-way, and 4-way inlet configurations, it complies with IS:904 standards and is ideal for commercial, industrial, and residential fire safety installations.
SPECIFICATIONS
Type:
2-way / 3-way / 4-way Dry Riser Inlet
Body:
Spheroidal Graphite Cast Iron (Ductile Iron)
Stainless Steel IS:3444 Grade 1 & Grade 4
Inlet:
Gun Metal / Stainless Steel
63mm Male Instantaneous NRV Connection
Outlet:
4 inch NB Flanged (2-way)
4 inch Flanged (3-way)
6 inch Flanged (4-way)
Size:
2-way – 100mm
3-way – 100mm
4-way – 150mm
Performance Test:
Hydrostatic Tested at 22 kgf/cm²
FEATURES
• Dry Riser Inlet manufactured in accordance with IS:904 standards.
• Body made of Spheroidal Graphite Cast Iron (Ductile Iron) for strength and durability.
• Inlet connections and non-return valves made of Gun Metal or Stainless Steel.
• Each inlet connection is fitted with a spring-loaded mushroom type non-return valve.
• Every Dry Riser Inlet is painted red internally and externally for fire safety identification.
• NRV (Non-Return Valve) covered with PVC cap or rubber cap for protection.